Two core
1.03 1/1.13 8.0 78 18.1 13 15 44 AP7 251/GL2520 UFPNF02
1.5 1/1.38 8.1 93 12.1 16.5 19.5 29 AP7 251/GL2520
2.5 1/1.78 9.5 140 7.4 23 27 18 AP9 251/GL2520 –
4.0 7/0.85 11.6 195 4.6 30 36 11 AP11 252/GL2520 –
Three core
1.03 1/1.13 8.2 88 18.1 13 15 44 AP7 251/GL2520 UFPNF02
1.5 1/1.38 8.4 116 12.1 16.5 19.5 29 AP8 251/GL2520 UFPNF04
2.5 1/1.78 10.4 180 7.4 23 27 18 AP10 252/GL2520 –
4.0 7/0.85 12.3 248 4.6 30 36 11 AP12 252 –
Four Core
1.03 1/1.13 8.5 107 18.1 13 15 44 AP8 251/GL2520 UFPNF04
1.5 1/1.38 10 143 12.1 16.5 19.5 29 AP9 251/GL2520 –
2.5 1/1.78 11.9 225 7.4 23 27 18 AP11 252/GL2520 –
4.0 7/0.85 13.5 310 4.6 30 36 11 AP13 254
1 Recommended clip spacing 300 mm horizontal and 400mm vertical. 2 Brass glands may be used as an alternative.
3 BS5266-1:2005 clause 9.2.3 states a minimum cross-sectional area of conductor of 1.5mm2
FP200 Gold?
is also available in multi-core versions (7,12 & 19 core)
Minimum recommended installation temperature 0?C. Installation methods for current rating in accordance with BS7671/IEE Wiring Regulations.
The tabulated ratings are based upon a 30?C ambient temperature and 70?C operating temperature. For other ambient temperatures or where cables
are grouped together, appropriate rating factors should be applied.
Key Applications
> Fire detection and fire alarm systems for buildings
> Voice alarm systems
> Emergency lighting
> Other essential service circuits
Cable Description
CONDUCTOR
Plain annealed copper solid (1.0 – 2.5 mm2
) or stranded
(4.0 mm2
) circular conductor complying with BS EN 60228
class 1 or class 2.
INSULATION
High performance damage resistant InsuditeTM
.
British Standard Type EI5.
Nominal
cross
sectional
area
mm2
Conceptual
Construction
no./mm
Mean
overall
diameter
mm
Approximate
cable
weight
kg/km
Maximum
conductor
resistance
at 20?C
ohms/km
Notes to table
FIRE RESISTANT CABLES 300/500V
Temperature ratings factor
Rating Factors for Groupings
Ambient Temperature?C 25 30 35 40 45 50
Rating factor 1.03 1.00 0.94 0.87 0.79 0.71
Number of circuits 2 3 4 5 6 7
Rating factor 0.80 0.70 0.65 0.60 0.57 0.54
FP200 GOLD?
BS7629-1:2008
INSTALLATION
Data Capability
Approvals
FP200 GOLD?
FIRE RESISTANT CABLES
> The original highly durable and dressable, easy to
terminate and install fire resistant cable, using the unique
InsuditeTM damage resistant insulation system. Approved
for fire detection and fire alarm critical signal paths to
BS5839-1:2002+A2:2008 and voice alarm systems to
BS5839-8:2008 in ?standard? application areas, and emergency
lighting systems to BS5266-1:2011.
The changes to cable test methods and requirements first
introduced by BS5839-1:2002 PH30, PH60 and PH120 mean fire
resistant cables are now approved to new test requirements.
> In addition to approvals to BS7629-1 and BS6387 Category
CWZ, FP200 Gold?
has received BASEC and LPCB approval to
BS5839-1:2002 for ?standard? applications. This includes approval to
BS EN 50200 Class PH30, PH60 and PH120 and the integrated fire,
shock and water test BS EN 50200 Annex E for 30 minutes.
All Prysmian FP200Gold?
cables are manufactured in the UK under an
ISO 9001 Quality System certified by BASEC and LPCB.
FP200 Gold?
meets the requirements of IS EN 50200:2006 PH120
classification as required by IS 3217:2008, and also the requirements
of IS EN 50200 Annex E.2 for 30 minutes Standard classification as
required by IS 3218:2009/ AC:2010
> FP200 Gold?
has excellent data/signal transmission characteristics
making it ideal for voice alarm, addressable and networked systems.
> In accordance with BS5839-1 and BS5266-1 requirements, cables
must be supported by a fixing that can withstand the same
fire conditions as the cable. To meet this requirement the use of
Prysmian AP LSOH?
coated metal P-clips or the new FP FirefixTM
rapid fixing system is recommended.
FP200 Gold?
should be installed in accordance with BS7671/IET
Wiring Regulations and/or other appropriate regulations or
codes. For outdoor installation use white sheathed cable, red
sheath requires additional suitable UV protection. Ideal for surface,
tray, direct burial in plaster or other methods that benefit from a
dressable product.
Certificate No 077f
Certificate No 077k
CABLE CHARACTERISTICS
Mechanical Impact
Medium
Temperature
Range
-20 to +70?C
Fire Resistance
BS6387 Category CWZ
BS EN 50200 PH30, PH60 & PH120
BS EN 50200 Annex E (30 mins)
Low Smoke Emissions
BS EN 61034-2
Halogen Free
BS EN 50267-2-1
Flexibility
Rigid
Fire Performance
BS EN 60332-1-2
BS EN 60332-3-21
Bending Radius
Fixed r=6D
Two core
1.03 1/1.13 8.0 78 18.1 13 15 44 AP7 251/GL2520 UFPNF02
1.5 1/1.38 8.1 93 12.1 16.5 19.5 29 AP7 251/GL2520
2.5 1/1.78 9.5 140 7.4 23 27 18 AP9 251/GL2520 –
4.0 7/0.85 11.6 195 4.6 30 36 11 AP11 252/GL2520 –
Three core
1.03 1/1.13 8.2 88 18.1 13 15 44 AP7 251/GL2520 UFPNF02
1.5 1/1.38 8.4 116 12.1 16.5 19.5 29 AP8 251/GL2520 UFPNF04
2.5 1/1.78 10.4 180 7.4 23 27 18 AP10 252/GL2520 –
4.0 7/0.85 12.3 248 4.6 30 36 11 AP12 252 –
Four Core
1.03 1/1.13 8.5 107 18.1 13 15 44 AP8 251/GL2520 UFPNF04
1.5 1/1.38 10 143 12.1 16.5 19.5 29 AP9 251/GL2520 –
2.5 1/1.78 11.9 225 7.4 23 27 18 AP11 252/GL2520 –
4.0 7/0.85 13.5 310 4.6 30 36 11 AP13 254
1 Recommended clip spacing 300 mm horizontal and 400mm vertical. 2 Brass glands may be used as an alternative.
3 BS5266-1:2011 clause 8.2.7 states a minimum cross-sectional area of conductor of 1.5mm2
FP200 Gold?
is also available in multi-core versions (7,12 & 19 core)
Minimum recommended installation temperature 0?C. Installation methods for current rating in accordance with BS7671/IEE Wiring Regulations.
The tabulated ratings are based upon a 30?C ambient temperature and 70?C operating temperature. For other ambient temperatures or where cables are
grouped together, appropriate rating factors should be applied.
Key Applications
> Fire detection and fire alarm systems for buildings
> Voice alarm systems
> Emergency lighting
> Other essential service circuits
Cable Description
CONDUCTOR
Plain annealed copper solid (1.0 – 2.5 mm2
) or stranded
(4.0 mm2
) circular conductor complying with BS EN 60228
class 1 or class 2.
INSULATION
High performance damage resistant InsuditeTM
.
British Standard Type EI5.
Core identification
Harmonised Core Identification:
o o brown-blue | o o o brown-black-grey
o o o o blue-brown-black-grey
non harmonised Core Identification:
o o red-black | o o o red-yellow-blue
o o o o black-red-yellow-blue
Non harmonised colours to special order.
SCREEN/CPC
Laminated aluminium tape screen bonded to sheath and in
contact with full size tinned annealed copper circuit protective
conductor which provides automatic screen earthing.
SHEATH
Robust thermoplastic LSOH sheath; Colour – White
or Red. Other colours to special order. For external
exposure the use of a white sheath is recommended.
Conceptual
Construction
no./mm
Mean
overall
diameter
mm
Approximate
cable
weight
kg/km
Maximum
conductor
resistance
at 20?C
ohms/km
Current
rating DC or
single phase
AC
Enclosed
Amps
Current
rating DC or
single phase
AC
Clipped direct
Amps
Volt drop
DC or single
phase
AC
mV/A/m
1
LSOH?
fixing
clips
2 Nylon
LSOH?
gland
Recommended accessories
Colour – White or Red
FP FirefixTM
fixing
clips
Notes to table
FIRE RESISTANT CABLES 300/500V
Temperature ratings factor
Rating Factors for Groupings
Ambient Temperature?C 25 30 35 40 45 50
Rating factor 1.03 1.00 0.94 0.87 0.79 0.71
Number of circuits 2 3 4 5 6 7
Rating factor 0.80 0.70 0.65 0.60 0.57 0.54
UFPNF01*
UFPNF02
* Single clip
Mechanical Impact
Medium Temperature
Range
-20 to +70?C
Fire Resistance
BS 6387 Category CWZ
BS EN 50200 PH30
BS EN 50200 Annex E
Low Smoke Emissions
BS EN 61034-2
Halogen Free
BS EN 50267-2-1 Flexibility
Rigid
Fire Performance
BS EN 60332-1-2
BS EN 50266-2-4
Bending Radius
Fixed r=6D
FP200 Gold? Multicore
BS7629-1:2008
>
>
>
>
FIRE RESISTANT CABLES
Plain annealed copper solid (1.0 – 1.5 mm2
) or stranded
(2.5 mm2
) circular conductor complying with BS EN 60228
class 1 or class 2.
High Performance damage resistant InsuditeTM.
British Standard Type EI5.
Laminated aluminium tape screen bonded to sheath and in
contact with tinned annealed coppper 0.5mm2
drain wire
which provides automatic screen earthing.
Conductor
Insulation
Screen
Core Identifi cation
Sheath Robust thermoplastic LSOH sheath
Colour – White or Red. Other colours to special order
For external exposure the use of a white sheath is
recommended.
>
Prysmian Cables & Systems Limited, Sales office, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK
Commercial Enquiries, Tel 0845 767 8345, Fax: 023 8029 5465
www.fpcables.co.uk
Ref: FP200Gold_Multi/01/09
Certifi cate No 077a
Certifi cate No 077b
7-12-19 cores white with printed number.
Key Applications > Fire detection and fi re alarm systems for buildings
Voice alarm systems
Emergency lighting
Other essential service circuits
1 Recommended clip spacing 300 mm and 400 mm vertical.
2 Brass gland may be used as an alernative.
3 This size is not included in the latest (2008) edition of BS7629-1 and is therefore manufactured to BS7629-1:1997
Installation methods for current rating in accordance with BS7671/IEE Wiring Regulations.
Minimum recommended installation temperature 0?C.
*The tabulated rating is as a two core and may be used where its number of cores carrying current does not exceed the square root of the total number of cores.
Notes to table
Temperature rating factors
Rating Factors for Grouping
Ambient Temperature ?C 25 30 35 40 45 50 55 60
Rating factor 1.03 1.00 0.94 0.87 0.79 0.71 0.61 0.50
Prysmian FP200 Gold? Multicore Cable
Prysmian Cables & Systems Limited, Sales office, Chickenhall Lane, Eastleigh, Hants, SO50 6YU, UK
Commercial Enquiries, Tel 0845 767 8345, Fax: 023 8029 5465
www.fpcables.co.uk
Ref: FP200Gold_Multi/01/09
1.0 1/1.13 12.1 196 18.1 13* 15* 44 AP12 252
1.5 1/1.38 13.3 249 12.1 16.5* 19.5* 29 AP13 252
2.5 7/0.67 16.3 387 7.4 23* 27* 18 AP16 254
Nominal
cross
sectional
area
mm
Conceptual
construction
no./mm
Mean overall
diameter
mm
Approximate
cable
weight
kg/km
Maximum
conductor
resistance
at 20?C
ohms/km
Current rating
DC or single
phase AC
Enclosed
Amps
Current
rating
DC or single
phase AC
Clipped direct
Amps
Recommended accessories
2
Nylon
LSOH
Gland
Volt drop
DC or single
phase AC
mV/A/m
Seven core
Twelve core
1.5 1/1.38 17.5 399 12.1 16.5 19.5* 29 AP18 254
2.5 7/0.67 21.7 637 7.4 23* 27* 18 AP22 255
Nineteen core
The tabulared ratings are based upon a 30?C ambient temperature and 70?C operating temperature.
For other ambient temperatures or where cables are grouped toghether, the following rating factors should be applied.
1.5 1/1.38 20.5 588 12.1 16.5 19.5* 29 AP20 255
2.53 7/0.67 25.6 949 7.4 23* 27* 18 AP25 –
Number of circuits 23456789
Rating factor 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50
1LSOH?
Fixing Clips
Sales enquiries
Tel: 0845 767 8345
Fax: 023 8029 5465
UK Technical helpline
Tel: 0845 767 8345
Fax: 023 8029 5002
Prysmian Cables & Systems Limited
Chickenhall Lane
Eastleigh
Hampshire
SO50 6YU
United Kingdom
www.prysmian.co.uk
www.fpcables.co.uk
Ref:FP200Gold/07/01/2013
Overseas sales enquiries
Tel: +44 (0) 23 5029 5481
Fax: +44 (0) 23 8029 5465
Overseas technical
Tel: +44 (0) 23 8029 5481
Fax: +44 (0) 23 8029 5002
Information hotline
Tel: +44 (0) 23 8029 5029
Fax: +44 (0) 23 8029 5437
A brand of the
Should you have any concerns about
unsafe, non-approved or counterfeit
cable, please contact the ACI
Tel: 020 8946 6978
Email: report@aci.org.uk
Sales enquiries
Tel: 0845 767 8345
Fax: 023 8029 5465
UK Technical helpline
Tel: 0845 767 8345
Fax: 023 8029 5002
Prysmian Cables & Systems Limited
Chickenhall Lane
Eastleigh
Hampshire
SO50 6YU
United Kingdom
www.prysmian.co.uk
For further information please
see our dedicaed FP Cables website:
www.fpcables.co.uk
SCAN THIS TO ACCESS www.fpcables.co.uk IN THREE SIMPLE STEPS.
1. Download any QR reader or barcode app for your smart phone.
2. Scan the QR code on the left your phone.
3. Access fpcables.co.uk instantly.





Reviews
There are no reviews yet.